How to Install Old Wired Smoke Detectors
Introduction
Smoke detectors are an essential safety device in any home. They can alert you to a fire in the early stages, giving you precious time to escape. Many homes still have older wired smoke detectors that were installed years ago. These older models may not have some of the newer features like interconnectivity, but they can still provide an important early warning. Updating to new smoke detectors is recommended, but in the meantime the old wired units can still be made functional. Installing them correctly is important for proper operation.
What You'll Need
- Old wired smoke detector
- Screwdriver
- Drill with assorted drill bits
- Wire stripper
- Voltmeter
- Electrical tape
- Drywall screws or anchors
Finding Power for the Smoke Detector
Older wired smoke detectors require a nearby power source to operate. This usually means tapping into a nearby electrical junction box. Options for providing power include:
-
Using an existing junction box that already powers another device like a light fixture. You can tee off the hot wire to also feed the smoke detector.
-
Running new wiring from a junction box to the desired smoke detector location. Use 14/2 or 12/2 NM electrical wire for this.
-
Using the electrical box for an existing switched light. Wire it ahead of the switch so the smoke detector is always powered on.
Always turn off the circuit breaker to the junction box before wiring a smoke detector to it. Test for power with a voltmeter before touching any wires.
Mounting the Smoke Detector
Smoke detectors should be mounted high on walls or ceilings, at least 4 inches from corners. Avoid installing near vents, windows, or anywhere that airflow could impact performance.
When mounting on a ceiling:
-
Position at least 4 inches from any wall.
-
Place it a minimum of 12 inches away from light fixtures to avoid false alarms.
When mounting on a wall:
-
Install within 12 inches of the ceiling.
-
Keep at least 4 inches clear on sides and below.
Use the provided mounting bracket and screws to secure the smoke detector. For drywall, use the provided anchors.
Wiring the Smoke Detector
Here are the steps for wiring an old smoke detector:
-
Cut power to the junction box you are using. Verify with a voltmeter.
-
Run 14/2 or 12/2 NM wire from the junction box to the smoke detector mounting bracket. Leave 6-8 extra inches at the detector for connections.
-
Strip 1/2 inch of insulation from the wire ends at the smoke detector. Connect the black (hot) wire to the connector marked "BLK". Connect the white (neutral) wire to the connector marked "WHT".
-
Connect the ground wire to the grounding connector on the mounting bracket.
-
Secure the wired connections with wire nuts and electrical tape.
-
Mount the smoke detector onto the bracket and screw it into place.
-
Restore power and test that the smoke detector powers on.
Testing and Maintaining Smoke Detectors
-
Press the "Test" button monthly to verify proper operation and that the alarm sounds.
-
Replace batteries on battery-powered units yearly.
-
Vacuum dust and cobwebs around smoke detectors regularly.
-
Consider updating to a newer interconnected smoke detector system for full fire protection.
-
Smoke detectors should be replaced every 8-10 years or according to manufacturer guidelines.
Conclusion
While newer smoke detectors have great benefits, older wired models can still provide protection if installed and maintained properly. By tapping into a nearby junction box for power and following safe mounting guidelines, they can continue alerting you in the event of smoke or fire. Just be sure to test them regularly and replace units that are over 10 years old.